Radio Telemetry Station Hardware

MP2600 SERIES

RADIO TELEMETRY STATIONS

 

Cost-Effective Wireless Solutions

  • 4-20mA analogs & digitals linked via radio

  • Fully earth-isolated inputs and outputs

  • Variety of configurations

  • Point-to-point or scanning topologies

 

The MP2600 series stations are general purpose radio telemetry stations providing bi-directional analog and digital wireless links.

The hardware is expandable using modular circuit boards to give the required I/O. The firmware is configured at the time of manufacture to give the necessary responses.

Solar or wind powered operation is feasible for any outstation not equipped with 4-20mA analog
I/O.

Outstation scanning is employed from the base station, sub-networks within the main network can be accommodated where necessary.

The stations are housed in IP65 enclosures, the number and dimensions of enclosures are dependent on the internal hardware. The general arrangement is with the electronics in the top half and terminal rails in the lower half accessible from a separate lid.

Various radio systems are available depending on the application. The standard radio system is licence-exempt in Europe.

Technical Details

General

Display

20 x 4 line dot matrix LCD

Update rate

Up to 4 outstations per second

Error-checking

CCITT 16 bit CRC

Operating Temperature

-20 to +60° C

Power Supply

230Vac (110Vac optional)

Radio System

MP2501 as standard (other Magenta modules optional)

Dimensions

Electronics enclosure: 270W x 170H x 150D (mm)
DIN rail enclosure, size 2: 270W x 270H x 135D (mm)
DIN rail enclosure, size 3: 270W x 540H x 135D (mm)
(DIN rail enclosure size determined by no.of connections)

Humidity

95% RH, non-condensing

Antenna Connector

N-type

 

Technical Details

Analog Inputs

Type

4-20mA current loop (internal or external loop-powered as requested at time of order)

Input Resistance

75 ohms

Resolution

12 bits

Maximum input current

40mA

Ground isolation

750Vac rms maximum

Technical Details

Analog Outputs

Type

4-20mA current loop, external loop power required

Output Resistance

100 ohms

Resolution

12 bits

Minimum exitation voltage

2V

Ground isolation

750Vac rms maximum

Technical Details

Digital Inputs

Type

Opto-isolated

Input Voltage

5-12Vdc

Input Resistance

1kohm

Ground isolation

750Vac rms maximum

Technical Details

Digital Outputs (open collector)

Type

NPN open collector

Current

30mA maximum

Voltage

30Vdc maximum

Technical Details

Digital Outputs (Relay)

Type

Changeover volt-free contacts

Current

10A maximum

Voltage

250Vac maximum